logo
Send Message

270mm CO2 Fire Extinguishing System CO2 Cylinders In UPS Room

1 set
MOQ
negotiation
Price
270mm CO2 Fire Extinguishing System CO2 Cylinders In UPS Room
Features Gallery Product Description Request A Quote
Features
Specifications
Cylinder Volume: 70Ltr
Capacity: 42kg
Pattern Of Extinguishing: Enclosed Flooding
Agent: CO2
Working Pressure: 5.7MPa
Max. Working Pressure: 12.4MPa
System Start Mode: Electrical Automatic, Electrical Manual, Mechanical Emergency Start
Discharge Time: ≤60s
Power: DC24V/1.6A
Internal Diameter: 270mm
Height: 1448mm
Highlight:

270mm CO2 Fire Extinguishing System

,

CO2 Fire Extinguishing System CO2 Cylinders

,

UPS Room CO2 Cylinders

Basic Infomation
Place of Origin: China
Brand Name: Air Giant
Certification: CAL,CMA,CNAS,ILAC-MRA,CCC
Model Number: QME70
Payment & Shipping Terms
Packaging Details: Plywood outer box with bubble bag or paper
Delivery Time: 10-15 working days
Payment Terms: L/C , D/P, T/T, Western Union, Paypal, Credit card
Supply Ability: 300 sets per week
Product Description

Cylinder For Enclosed Flooding CO2 Fire Extinguishing System In UPS Room

 

Carbon Dioxide (CO2) is an excellent fire suppression agent. It has been used in the fire protection industry for many years, and is listed under NFPA-12 Carbon Dioxide Fire Extinguishing Systems. CO2 is used for a variety of systems; including total flooding, local application, and inerting.

 

CO2 extinguishes a fire by removing the oxygen from the surrounding area, and for local application type systems, breaks the fire triangle by removing the heat. Because of the safety considerations when using CO2, it is only used for very specific applications, and not where the hazards are occupied. Please consult AFT with any questions using CO2. It can be supplied in high pressure and low pressure storage tanks.

 

Being one of the major players in the power generation fire protection industry, it is not uncommon to supply a 6 ton storage tank for a turbine site. For many industrial applications, we supply high pressure CO2 cylinders. We also supply the associated detection and control equipment required. If you would like to speak with us regarding CO2 fire suppression systems, please feel free to contact us.

 

 

Parameters

 

No. Specification Technical Parameter
1 Device Model QME70
2 Capacity 70Ltr
3 Filling Volume of Gas 42kg
4 Working Pressure 5.7MPa
5 Max Working Pressure 12.4MPa
6 Spraying Time ≤60s
7 Max Filling Rate 0.6kg/L
8 Power DC24V/1.6A
9 Working Pressure of Releasing Device

Container Valve: 19±0.95MPa;

Manifold: 15±0.75MPa

10 Nitrogen Pressure of Driving 6.0±1.0Mpa(20℃)
11 Condition of Reserving Room for Container Temperature: 0~50℃
 
 

Application

 

Library and archives room, electronic computer room, electrical substation, telecommunication room, hangar, garage, cargo, paint-spraying room, boiler room, control center, etc.

 

It is suitable for putting out all kinds of the fires of flammable liquid and solid matter; gas fire in which power can be cut off before extinguishing the fire.

 

 

Package

 

We always pack it with polyfoam firstly and then put it into a wooden case. Sometimes, in order to meet with customers or the safety requirement, we will make a pallet for the goods.