Inert Gas Fire Suppression Solutions (IG-55, IG-541 And IG-100)
Description:
When a fire is detected, the IG55 system releases the inert gas mixture into the protected space. The gases quickly disperse, reducing the oxygen concentration to a level where the fire cannot sustain itself. The process is fast, efficient, and leaves no residue, ensuring minimal downtime and no secondary damage.
The IG55 fire extinguishing system is a reliable, sustainable, and effective solution for protecting critical infrastructure and assets from fire hazards. Its unique properties make it a preferred choice for industries where safety, environmental impact, and asset protection are paramount.
Technical parameters of IG55 fire suppression system
Working temperature (℃) |
0℃~+50℃ |
||
Working pressure |
Storage pressure |
20.0MPa |
30.0MPa |
Max. working pressure (+50℃) |
23.2MPa |
36.6MPa |
|
Min. working pressure (-20℃) |
18MPa |
27MPa |
|
Container volume (L) |
80L |
140L |
|
Filling weight (kg, @200 bar) |
22.32kg |
39.06kg |
|
Filling weight (kg, @300 bar) |
33.48 kg |
58.59kg |
|
System operating voltage |
220V AC,24V DC |
||
System start mode |
Electrical automatic, electrical manual, mechanical emergency start |
||
Design concentration |
Class A dangerous material surface fire |
40.3% |
|
Class B |
47.6% |
||
The design concentration of the protective zone with people working |
40.3%~43% |
Storage cylinder group, storage cylinder group frame, nitrogen driving device, nitrogen driving device frame, the cylinder valve, liquid flow check valve, air flow check valve, electromagnetic starter, gas conveying pipeline, collecting pipe, choice valve, three links, reducer tee, reducing elbow, flange, safety valve, pressure transmitter, pipe, nozzle, chemicals, fire detector, fire controller, sound and light alarm, alarm bell, gas light, emergency start / stop button, etc.
-- Suitable for Occupied Areas
-- Electrically Non-Conductive
-- Chemically Inert
-- Colourless, Odourless, and Flavourless
-- No Residue
-- Zero Ozone Depletion Potential (ODP)
-- No Greenhouse Effect
-- No Decomposition Products
-- No Fog and No Loss of Post-Discharge Visibility
-- Non-Corrosive/Toxic
-- Stored as a Gas
-- Excellent Post-Discharge Visibility
-- Very Low Refill Cost
-- Easy to Obtain Anywhere in the World
- Computer rooms
- Telecommunication center
- Facilities underground
- Offshore oil extraction
- Library
- Data and paper archives
- Valuable article storage
- Power generator storage room