Hanging FM200 System Without Pollution For Museum
Description
Hanging type FM-200 fire extinguisher is a preset and independent fire extinguishing system. It is easily wall or ceiling mounted in the protected area to directly put out the fire, without pipe network distribution.
The electromagnetic actuated hanging extinguisher has two activation methods. When control panel receives signal from smoke/heat detector of fire alarm, it will send signal to electromagnetic extinguisher automatically which opens container valve, so to discharge fire extinguishing agent. It also could be activated by manual control button.
Parameters
No | Specifications | Parameters |
1 | Tank size | 16Ltr, 20Ltr, 30Ltr |
2 | Device model | XQQC16/1.6, XQQC20/1.6, XQQC30/1.6 |
3 | Storage pressure | 1.6MPa |
4 | Maximum working pressure | 2.5MPa |
5 | Discharge time | ≤8s |
6 | Maximum filling rate | 1kg/L |
7 | Device starting power | DC24V/1.6A |
8 | Environment temperature of protection zone | 0℃~50℃ |
Below data refers to regular temperature at 20 centigrade and atmospheric pressure at 1 bar. The max coverage would vary a little from the ambient temperature and pressure on the real condition.
Device model | Filling amount (kg) | Maximum working pressure(Mpa) | Storage pressure (Mpa) | Maximum coverage (m³) |
Starting mode |
XQQC16/1.6 | 16 | 2.5 | 1.6 | 22.22 |
Starting power:
Solenoid actuator |
XQQC20/1.6 | 20 | 2.5 | 1.6 | 27.78 | |
XQQC30/1.6 | 30 | 2.5 | 1.6 | 41.67 |
Components
One spherical pressure tank, fire extinguishing agent(HFC-227ea, same as FM200), hanging mounting, thermal sensor(one little glass tube filled with liquid whose volume will be changed by temperature), pressure switch, stainless steel pipe and nozzle.
Packages
We always pack it with polyfoam first and then put it into a wooden case. Sometimes, in order to meet with customers or the safety requirement, we will make a pallet for the goods.