Send Message

Hfc227ea Fire Suppression System Without Pollution for Computer Room

1 set
MOQ
negotiation
Price
Hfc227ea Fire Suppression System Without Pollution for Computer Room
Features Gallery Product Description Request A Quote
Features
Specifications
Storage Pressure: 4.2 MPa
Spraying Time: ≤10s
Filling Density: ≤950kg/m3
Nominal Pressure: 5.3MPa
Test Pressure: 8.4MPa
Working Power: DC 24V 1.6A
Working Temperature: 0℃~50℃
Protected Zone Range: Proportion: ≤800m² ; Volume: ≤3600m³
Starting Mode: Automatic, Electrical Manual, Mechanical Manual
Cylinder Volume: 40L、70L、100L、120L、150L、180L
Basic Infomation
Place of Origin: China
Brand Name: Air Giant
Certification: CAL,CMA,CNAS,ILAC-MRA,CCC
Model Number: QMP40/4.2, QMP70/4.2, QMP100/4.2, QMP120/4.2, QMP150/4.2, QMP180/4.2
Payment & Shipping Terms
Packaging Details: Plywood outer box with bubble bag or paper
Delivery Time: 10-15 working days
Payment Terms: L/C, D/P, T/T, Western Union, Paypal, Credit card
Supply Ability: 28000 sets per week
Product Description

Hfc227ea Fire Suppression System Without Pollution for Computer Room

 

HFC-227ea(FM200) clean agent automatic fire suppression system is widely used in China and all over the world. Its most strong point is that this system meets the world’s requirement of environmental protection. It will not hurt the ozone layer even for 1% possibility. The other strong point is that such as the clean, odorless and colorless agent, the easy installation and so on, make it the best substitute for the halon 1301 in people’s mind.

 

Fm200 gas fire suppression system works more efficient when it is equipped with the electric elements. Besides, this system requires a little storage room outside but next to the protected zone. It helps save places. This system also distinguishes itself by the fast spraying time with less than 10s.

 

 

Components

 

Actually, a complete fire suppression system has two parts, one is fire extinguishing part and the other is electrical elements part. Because there is a part focus on eletrical elements, so here will not talk about it anymore. The fire extinguishing part is list out as followings:

1/ Fm200 cylinder

2/ Container valve

3/ Solenoid actuator

4/ Flexible hose

5/ Liquid flow check valve

6/ Cylinder frame

7/ Manifold

8/ Safety valve

9/ Pressure switch

Hfc227ea Fire Suppression System Without Pollution for Computer Room 0

 

 

 

Application

 

As its name says, the single zone pipe network fm200 fire suppression system is suitable for a single protected zone, whose volume should be less than 3600 cubic meters as well as proportion should be less than 800 square meters. Because of its property and principles of putting off fire, the single zone pipe network fm200 fire suppression system can be used to protect some large and also significant places, such as the followings:

 

- Computer rooms

 

- Telecommunication center

 

- Facilities underground

 

- Offshore oil extraction

 

- Library

 

- Data and paper archives

 

- Valuable article storage

 

- Power generator storage room

 

 

Advantages

 

This system has a cylinder frame, whose shape is similar to a cabinet, so this system is called cabinet pipe network type fm200 fire suppression system. Besides, here is going to list out the advantages of this system.

 

1/ Place saving. This fire suppression system requires a separated room outside the protected zone, and will not occupy the places of the protected zone.

 

2/ Easy installation. A few components and an easy structure make the system install easily.

 

3/ Convenient transportation. Because of a few components and careful package, the transportation will be very convenient and safe.

 

 

Packages

 

We always pack it with polyfoam firstly and then put it into a wooden case. Sometimes, in order to meet with customers or the safety requirement, we will make a pallet for the goods.